GS Silicone Cable – Thermal Class H 180°C
Red or tinned copper, standard strands, extruded silicone rubber
Red or tinned copper, standard strands, extruded silicone rubber
CHARACTERISTICS:
Extruded silicone rubber
Rated voltage: Uo/u 300/500 V
Test voltage: 2000 Volts
Good resistance to aging and
Mechanical strength: low
weathering :ozone, U.V. etc...
Operating temperature: -60° to +180 ºC, tips up to 230 ºC
APPLICATIONS:
Wiring of heating appliances.
Electric motors, transformers, generators
Luminaires.
Industrial wiring in hot environments.
Sez. | Diam.filo | Resistenza elettrica max. | Resistenza elettrica max. | Spess. | diam.est. |
0,35 | 0,21 | 55,70 | 57,30 | 0,6 | 1,90 |
0,50 | 0,21 | 39,0 | 40,1 | 0,6 | 2,10 |
0,75 | 0,21 | 26,0 | 26,7 | 0,6 | 2,40 |
1,00 | 0,21 | 19,5 | 20,0 | 0,6 | 2,50 |
1,50 | 0,26 | 13,30 | 13,7 | 0,6 | 2,80 |
2,50 | 0,26 | 7,98 | 8,21 | 0,7 | 3,40 |
4,00 | 0,31 | 4,95 | 5,09 | 0,8 | 4,20 |
6,00 | 0,31 | 3,30 | 3,39 | 0,8 | 5,00 |
10,0 | 0,41 | 1,91 | 1,95 | 1,0 | 6,20 |
16,0 | 0,41 | 1,21 | 1,24 | 1,2 | 7,50 |
25,0 | 0,41 | 0,780 | 0,795 | 1,4 | 9,00 |
35,0 | 0,41 | 0,554 | 0,565 | 1,4 | 10,20 |
50,0 | 0,41 | 0,386 | 0,393 | 1,6 | 13,00 |
70,0 | 0,51 | 0,272 | 0,277 | 1,6 | 14,60 |
95,0 | 0,51 | 0,206 | 0,210 | 1,8 | 18,00 |
120 | 0,51 | 0,161 | 0,164 | 1,8 | 19,00 |
150 | 0,51 | 0,129 | 0,132 | 2,0 | 21,40 |
185 | 0,51 | 0,106 | 0,108 | 2,2 | 23,60 |
240 | 0,51 | 0,082 | 0,083 | 2,4 | 26,50 |